Cleanroom Differential Pressure Is Not Always ≥10Pa: First Clarify Where 5Pa and 10Pa Are Applied, Then Determine Air Change Rates and Cross-Sectional Velocities According to Standards

Cleanliness depends on pressure differential, air change rate and face velocity together. Under GB 50073-2013, 10 Pa is the minimum versus outdoors, and 5 Pa applies between clean and non-clean zones and between grades. For pharmaceutical plants, GB 50457-2019 requires at least 10 Pa in all three cases. ACH ranges apply only to non-unidirectional rooms under 4.0 m; unidirectional rooms use face velocity. Supply air must also cover heat, moisture and outdoor air; pressure is a supply/return/exhaust balance.

— 暖心技术团队

Whether a cleanroom can maintain its cleanliness level depends not on a single number, but on three parameters working together: differential pressure prevents uncontrolled infiltration from outside; air changes per hour (ACH) dilute internally generated particles in non-unidirectional flow rooms; face velocity directionally removes particles in unidirectional flow rooms. These three quantities are often cited in the same table, and are also frequently confused—especially treating "≥10 Pa" as a uniform lower limit between clean zones and non-clean zones, or reversing the ACH values for Class 10,000 and Class 100,000.

Below, the basis for values, mutual conversion, and the most common failure points during acceptance inspection are clarified at once according to current standards. First, the reference table:

TALK TO AN ENGINEER / 直接问工程师

把您的温湿度工况发来,我们帮您核算。

免费选型建议 · 15 年行业经验 · 常规交期约 15 天

ParameterFunctionTypical ValueBasis
Differential PressurePrevent uncontrolled infiltration and maintain directional airflowBetween cleanrooms of different classes: should not be less than 5 Pa; between clean zone and non-clean zone: shall not be less than 5 Pa; between clean zone and outdoors: shall not be less than 10 PaGB 50073-2013 Clause 6.2.2. For pharmaceutical cleanrooms, refer to GB 50457-2019, where all three locations shall not be less than 10 Pa
Air Changes per HourDilute internally generated particles in non-unidirectional flow roomsISO Class 8 (Class 100,000) 10–15 ACH; ISO Class 7 (Class 10,000) 15–25 ACH; ISO Class 6 (Class 1,000) 50–60 ACHGB 50073-2013 Table 6.3.3. Applicable for rooms with floor-to-ceiling height less than 4.0 m; values also depend on personnel, equipment, and materials; table values are static references
Face VelocityDirectional particle removal in unidirectional flow roomsISO Class 1–3: 0.3–0.5 m/s; ISO Class 4–5: 0.2–0.4 m/s