INDUSTRIAL DEHUMIDIFYING HEAT PUMP · NX-FL2000BP-5 SERIES
The 5RT inverter heat-pipe dehumidifying heat pump dries and cools in one cycle: its heat-pipe energy module pre-cools incoming air for free, and condenser waste heat reheats the dry air for free — no electric reheat, no second machine.
Tested at 29°C / 65% RH: 12 kW cooling + 11 kg/h dehumidification
FIELD-PROVEN · ±1°C / ±5%RH · OEM/ODM · TYPICAL LEAD TIME ~15 DAYS



WHAT YOU GET
Everything below comes from one cabinet. The heat-pipe energy module is what makes the numbers possible.
Against a “dehumidifier + air conditioner” stack for the same duty, modelled input drops to about 31.5%. The heat-pipe module pre-cools air with zero power — that is where the saving starts.
One unit replaces an industrial dehumidifier and an air conditioner — 12 kW cooling + 11 kg/h dehumidification from the same cycle, with no electric reheat heater to buy or wire.
Precision ±1°C / ±5% RH with a supply-air dew point down to −3°C — stable enough for food, pharma, laboratory and cleanroom production.
01 / PROBLEMS WE SOLVED
From a Foshan food-factory retrofit. Each row pairs a documented plant problem with how one water-cooled 5RT inverter heat-pipe dehumidifying heat pump addressed it. Case pain numbers are shown as tags. Target room condition in that project: roughly 22–24°C / 42–50% RH.
Humidity missed target in humid seasons; extra portable dehumidifiers were added.
One unit holds ±1°C / ±5% RH.
±1°C / ±5% RH
The plant used chilled water for cooling and dehumidification, then cooling-water heat for reheat. In monsoon / “return-south” weather, humidity often missed the target. Operators added portable industrial dehumidifiers while the custom air-handling cabinet lost humidity control. The loop also needed two pump stages, with cooling water fixed at about 30°C in / 35°C out.
One water-cooled 5RT heat-pipe unit handles temperature and humidity together — precision ±1°C / ±5% RH — without depending on that chilled-water + reheat cabinet for moisture control in humid seasons.
Only 3.53% of chilled-water cooling went to moisture removal.
Effective dehumidification cooling raised to 61.12%.
≈17×
Chilled-water dehumidification wastes most of the cooling on sensible load. In the supplied comparison (about 24°C / 45% RH), only 3.53% of cooling was effective for moisture removal.
Direct-expansion with heat-pipe heat recovery raised effective dehumidification cooling to 61.12% in the same comparison framework — about 17× the conventional share. See the case table below for full power rows.
Insulated chilled-water pipes drip condensate; re-insulation costs >RMB 100,000 per cycle.
No chilled-water pipe insulation needed for dehumidification.
>RMB 100,000
Chilled-water pipes need insulation. Damaged jackets drip condensate into the production area — unacceptable for food hygiene. Lower water temperatures raise viscosity and pump power. Insulation replacement every ten-plus years was estimated at more than RMB 100,000 per cycle.
The heat-pipe scheme does not rely on chilled-water pipe insulation for dehumidification. Engineering scope shrinks, and the recurring insulation-replacement cost for that loop goes away.
Desiccant wheel used 3–4 t of steam per day; rotor replaced about every 7 years.
No steam loop; about 10% of the energy in the case comparison.
~10%
Desiccant-wheel systems in referenced projects used about 3–4 tonnes of steam per day (steam priced at more than RMB 300/tonne) and needed rotor replacement roughly every 7 years, with costs reaching hundreds of thousands of RMB.
The heat-pump approach avoids that steam loop for this duty. In the case comparison, the supplied heat-pump system used about 10% of the energy of the referenced desiccant-wheel equipment (project-specific — recheck for each duty).
Ordinary dehumidifiers give ~2.1 kg/kW, add heat and still need an AC.
4.4 kg/kW plus 12 kW cooling in one unit.
≈68.5%
Ordinary industrial dehumidifiers only control humidity. At nominal conditions they deliver about 2.1 kg/kW of moisture removal and add heat to the room — so a separate air conditioner is still required.
NX-FL2000BP-5 delivers about 4.4 kg/kW moisture removal in the case note, plus useful cooling from the same cycle. At 29°C / 65% RH: 12 kW cooling + 11 kg/h dehumidification — one unit instead of dehumidifier + AC. Modelled input for an equivalent duty is about 31.5% of that stack (≈ 68.5% saving).
Only one aging room, so product was moved there repeatedly.
Stable local control keeps process rooms on condition.
5RT
The site had only one aging room, so product (sugar) had to be moved there repeatedly — high labor load and operating friction.
Stable local temperature/humidity control with the 5RT unit supports keeping process rooms on condition without routing everything through a single aging room. Exact layout gains are project-specific.
Pain numbering follows the Foshan food-factory case file. Retrofit hardware: one water-cooled 5RT inverter heat-pipe dehumidifying heat pump. Results are project-specific.
02 / HOW IT WORKS
The heat pipe pre-cools incoming air toward saturation; condenser waste heat then reheats the dry air to the target temperature — without electric heaters.
Raises dehumidification efficiency by up to 44% with no extra energy for air pre-treatment.
Reuses available heat from the cooling process to bring low-temperature dry air up to the supply setpoint — no electric heater.
Process diagram values from the product catalog (illustrative air path).
03 / COMPARISON
Full parameter comparison vs a conventional industrial dehumidifier used as the baseline (CFZ6.3B). Our columns are NUNXIN NX-FL2000BP-5 water-cooled, air-cooled integrated and air-cooled split. Modelled energy use vs a dehumidifier + air-conditioner pair is about 31.5% of that stack (≈ 68.5% saving). Versus a referenced desiccant-wheel system, energy use is about 10%.
Table 1 — Conventional industrial dehumidifier (CFZ6.3B) vs NUNXIN NX-FL2000BP-5
| Parameter | Conventional industrial dehumidifier (CFZ6.3B) | NUNXIN NX-FL2000BP-5 Water-cooled |
NUNXIN NX-FL2000BP-5 Air-cooled integrated |
NUNXIN NX-FL2000BP-5 Air-cooled split |
Difference (ours vs conventional) |
|---|---|---|---|---|---|
| Nominal dehumidification (kg/h, 27°C / 60% RH) | 6.3 | 10 | 10 | 10 | +58.7% (10 − 6.3) / 6.3 |
| Nominal dehumidification (kg/h, 27°C / 70% RH) | 8 | 11 | 11 | 11 | +37.5% (11 − 8) / 8 |
| Power supply (V) | 3N~380V/220V ±10% | 380V~480V | 380V~480V | 380V~480V | Wider range |
| Frequency (Hz) | 50 | 50 / 60 | 50 / 60 | 50 / 60 | Wider range |
| Rated current (A) | 7 | 3.9 | 5.51 | 5.51 | −44.3% water-cooled (3.9 vs 7); air-cooled −21.3% (5.51 vs 7) |
| Rated input power (kW) | 3.8 | 2.5 | 3.5 | 3.5 | −34.2% water-cooled (2.5 vs 3.8); air-cooled −7.9% (3.5 vs 3.8) |
| Maximum input power (kW) | 4.36 | 3.20 | 3.70 | 3.70 | −26.6% water-cooled (3.20 vs 4.36); air-cooled −15.1% (3.70 vs 4.36) |
| Power factor | 0.80 | 0.98 (all brushless motors) | 0.98 (all brushless motors) | 0.98 (all brushless motors) | +0.18 0.98 vs 0.80 |
| Circulating airflow (m³/h) | 1,800 | 500–2,000, EC inverter load-matching | 500–2,000, EC inverter load-matching | 500–2,000, EC inverter load-matching | Variable EC range vs fixed 1,800 |
| Suction pressure (MPa) | 0.60 | 0.60 | 0.60 | 0.60 | Same |
| Discharge pressure (MPa) | 1.88 | 2.10 | 2.30 | 2.30 | Architecture-specific |
| Noise (dB(A)) | ≤60 | ≤60 | ≤60 | ≤60 | Same class |
| Refrigerant / charge (kg) | R22 / 1.9 | R410A / 1.8 | R410A / 1.8 | R410A / 1.8 | R410A vs R22 |
| Dimensions D×W×H (mm) | 430×600×1,920 | 1,068×468×1,694 | 1,068×468×1,694 | 1,068×468×1,694 | Different footprint |
| Mass (kg) | 132 | 200 | 200 | 200 | +68 kg |
| Breaker / start current | ≥25 / 15 A setpoint class | Soft start, start current <1 A | Soft start, start current <1 A | Soft start, start current <1 A | <1 A soft start vs ≥15 A class |
| Indoor thermal effect / cooling | Adds heat to the room (~2.57 kW heat per kW input) — needs a separate AC | 12 kW cooling + 11 kg/h dehumidification at 29°C / 65% RH — one unit replaces dehumidifier + AC | +12 kW cooling vs none / adds heat | ||
| Moisture per input power (case note) | ~2.1 kg/kW | ~4.4 kg/kW | +109.5% (4.4 − 2.1) / 2.1 | ||
Cooling and simultaneous dehumidification (12 kW + 11 kg/h) tested at 29°C / 65% RH. Spec rows from the product comparison table in the Foshan case materials. Percentage differences use water-cooled figures where three NUNXIN columns share the same value, or are stated per configuration when they differ. Final performance depends on moisture load, target dew point, climate and selection.
CFZ6.3B 6.3 kg/h → NUNXIN 10 kg/h
+58.7% at 27°C / 60% RH
3.8 kW → 2.5 kW
−34.2%
0.80 → 0.98
+0.18 · all brushless
≥15 A class → <1 A soft start
Soft start
Adds heat · needs AC → 12 kW cooling
+11 kg/h at 29°C / 65% RH
R22 → R410A
Modern charge 1.8 kg
04 / FIELD EVIDENCE
Target roughly 22–24°C / 42–50% RH. Existing chilled-water dehumidification with cooling-water reheat could not hold humidity in monsoon weather. Retrofit: one water-cooled 5RT inverter heat-pipe unit. Full write-up on the official site: nunx-tec.com/strength/28.
Table 2 — Humidity-treatment power comparison (deep-cool approaches)
| Metric | Conventional deep-cool (12°C) | Heat-pipe heat-recovery approach (2°C) | Difference |
|---|---|---|---|
| Effective cooling used for dehumidification | 3.53% | 61.12% | ≈17.3× 61.12 / 3.53; +57.59 pp |
| Cooling required for 50 kg/h moisture removal | 424.70 kW | 105.00 kW | −75.3% (105.00 − 424.70) / 424.70 |
| Reheating required | 380.00 kW | 69.00 kW | −81.8% (69.00 − 380.00) / 380.00 |
| Airflow | 8,500 CMH | 9,000 CMH | +500 CMH |
| Equivalent cooling-source power | 86.36 kW | 6.90 kW | −92.0% (6.90 − 86.36) / 86.36 |
| Electric reheating | 380.00 kW | 0 kW | −100% |
| Total calculated power | 466.36 kW | 6.90 kW | −98.5% (6.90 − 466.36) / 466.36 |
Source note uses a 25°C / 45% return-air condition with constant-temperature supply. Actual installations may not require constant-temperature supply — total calculated power can differ from field results for that reason. Results are project-specific and depend on process load, climate, equipment selection and operating conditions.




FIELD CASE / 18 m² LAB
In an 18 m² laboratory, cooling alone is not enough: low humidity also calls for stable temperature. A conventional solution often combines precision air conditioning with separate dehumidification and reheat. NUNXIN integrates both controls in one unit, reducing operating power and solution cost for this project.
Temperature and humidity control targets
Average operating power: 1.5 kW vs 18 kW for the conventional solution
Approximately 92% lower average power
Solution cost: 30–50% of the conventional solution
Project figures provided by the customer on site; actual results vary with load and operating conditions.
04B / TYPICAL CASES
Six featured field projects from nunx-tec.com/strength — food, pharma, laboratory and casting. Each card opens the official English case page in a new tab; use View all cases for the full listing.

Foshan food factory retrofit with a water-cooled 5RT variable-frequency heat-pipe dehumidification heat pump; case notes 4.4 kg/kW at 27°C/70% vs ~2.1 kg/kW for a typical industrial dehumidifier.
Read case study →
Dongguan Taiwanese-funded snack workshop (8th year of purchasing); ~300 m², 6 m height, target about 23°C and below 45% RH, replacing desiccant-wheel dehumidifiers.
Read case study →
France Schneider precision air-conditioning enthalpy laboratory; humidity needed below 20%, where a customer-bought 10P industrial dehumidifier could not reach the target.
Read case study →
Chengdu pharmaceutical cephalosporin solid-preparation cleanroom fresh-air dehumidification; listing notes stable 50–60% RH control with dew point as low as 3–5°C.
Read case study →
Gummy production workshop case for low dew-point variable-frequency air-cooled temperature and humidity control, described as halving dehumidification energy use.
Read case study →
Precision-casting foundry retrofit with heat-pipe inverter dehumidifier; case comparison reduced operating power from 145 kW to 11.7 kW versus chilled water + electric heat.
Read case study →Titles and summaries are taken from the official case listing/pages. Performance figures on those pages are project-specific.
05 / MODELS
NX-FL2000BP-5 series — Mitsubishi inverter compressor, EC fan, airflow 500–2,000 m³/h, R410A. At 29°C / 65% RH: 12 kW cooling with 11 kg/h dehumidification.
NX-FL2000BP-5
NX-FL2000BP-5
NX-FL2000BP-5
Catalog includes operating modes, installation sketches and parameters. Power supply 380V~480V / 50Hz or 60Hz.
06 / APPLICATIONS
07 / SIZING
Share five engineering inputs. We open WhatsApp with a prefilled brief — no backend, no waiting for a form email.
08 / FAQ
Answers drawn from the Foshan food-factory engineering Q&A — written for overseas plant and OEM buyers. Where a number is project-specific, we say so.
A conventional cabinet typically uses chilled water to cool and dehumidify, then cooling-water heat to reheat. Our heat-pipe scheme uses direct expansion with heat-pipe and condenser heat recovery for reheat; surplus heat leaves through an outdoor exchanger or water. In the supplied plant comparison, effective moisture-removal cooling was about 3.53% for the conventional approach vs 61.12% for the heat-pipe approach (about 17×). Chilled-water pipe insulation is not required for our dehumidification path, so drip risk and periodic insulation replacement for that loop are avoided.
At the case’s 27°C / 70% RH note, moisture removal per input power is about 4.4 kg/kW vs 2.1 kg/kW for a typical industrial dehumidifier. The conventional unit adds heat to the room (~2.57 kW heat per kW input) and still needs an air conditioner; ours delivers cooling from the same cycle — 12 kW cooling + 11 kg/h at 29°C / 65% RH. For an equivalent treatment duty, the case models a dehumidifier + AC (COP 5.0) at about 3.18 kW input vs 1 kW for the heat-pipe unit — about 31.5% of that stack, or roughly 68.5% less energy. Full CFZ6.3B vs NX-FL2000BP-5 rows are in the comparison table. Heat-pipe recovery also reduces the performance drop that ordinary dehumidifiers show as target humidity falls.
Typical maintenance is regular filter replacement and heat-exchanger cleaning. There is no chilled-water pipe insulation cycle to replace for the dehumidification path.
In the referenced comparison, the supplied heat-pump system used about 10% of the energy of the desiccant-wheel equipment. Desiccant projects in the case used roughly 3–4 tonnes of steam per day and rotor replacement about every 7 years. Treat the 10% figure as project-specific and recheck for each duty, climate and load.
At a recirculating-air condition of 25°C / 45% RH, the case states approximately 7 kg/h of moisture removal. Confirm against your moisture load and selected configuration.
In a sealed clean room with no exhaust and no internal heat sources, one unit can provide temperature and humidity control for about 30 m² at roughly 22–24°C / 42–50% RH. Larger rooms, exhaust, or process heat need a fresh load calculation.
In the Foshan case, the central plant held cooling water at a fixed 30°C / 35°C, which limited year-round performance. With the inverter heat-pipe unit taking the humidity duty, cooling-water temperature can follow wet-bulb instead. Foshan’s annual average wet bulb is given as 19.8°C; under that framing the central plant was estimated to cut energy by about 24.4% (lower condensing temperature → higher COP). Recalculate for your climate and plant controls — this is a project estimate, not a universal guarantee.
We have supplied Hsu Fu Chi (Dongguan) continuously for 8 years; many of their workshops use our equipment, and they have been replacing Munters desiccant wheels and Hitachi chillers with our units over time. A customized project for a Guangdong sports-equipment manufacturer reported electricity-cost savings of over RMB 1 million per year in their statistics. Ask for the case pack that matches your industry.
Dual heat recovery lets one compression cycle deliver dehumidification and useful cooling — so one unit can replace a dehumidifier plus a separate air conditioner. At the tested condition of 29°C / 65% RH, the unit delivers 12 kW cooling together with 11 kg/h dehumidification.
Yes. Project-specific selection, control integration, factory testing and OEM/ODM cooperation are supported. Share your market, target condition and cooperation model on WhatsApp.
Typical lead time is about 15 days; confirmed per order based on configuration and quantity. Ask on WhatsApp for the current schedule for your model.
FAQ figures are tied to the Foshan food-factory case materials and related product table. Final energy use, moisture removal and cooling depend on process load, climate, equipment selection and operating conditions.